Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-RES-0623-05815
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/12/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0623-05815 (230 S BIRCH PL TUCSON, AZ 85710) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. The 1β pipe to the Furnace and Tankless water heater is underside. The given length (45β) and demand (385k BTUh) requires a 1 ΒΌβ pipe, Table G2413.4(1) Metallic Pipe. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 06/09/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |