Permit Number: TC-RES-0623-05749
Parcel: 116123990

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.3

Permit Number - TC-RES-0623-05749
Review Name: RESIDENTIAL NEW DWELLING v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/11/2023 Site Zoning APPROVED
07/11/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/10/2023 Residential Building REQUIRES RESUBMIT TC-RES-0623-05749 R1
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance with component sizes. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Plans should include all changes and alterations for a functional code compliant completion. A final inspection cannot be processed until all utilities are installed and operational. Include the permit numbers on the site plan for construction not shown in this plan set.

Provide a clear and concise construction plan set. Sample plans are available at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

SITE PLAN:

Provide permit numbers of work performed in support of the kitchen, den to bedroom, utility, and bathroom alterations. Otherwise, include changes for code compliance in this plan set, R106.1.1.

FLOOR PLAN:

1. Clarify if the new walls are replacing existing walls requiring removal or if the second bedroom and utility room are new rooms constructed under an existing roof structure or new building additions.
2. Show compliance with R310 providing egress from bedrooms with minimum clear opening height of 24”. The 48” high DH window shown on page #2 has an undersized opening.

SECTIONS - DETAILS:

1. An unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Show a roof design with insulation types and minimum thickness for meeting the condensation control requirement and the minimum total insulation value of R-38 or R-30 when extended over the wall top plate for additions under 500 SF.

PLUMBING PLANS:

1. Provide complete plumbing plans showing any changes with 2018 IRC compliance, R301.1. Include the permit number for any alterations performed in the rooms shown for renovation on the site plan.

MECHANICAL PLANS:

1. Show heating facilities in all habitable rooms, R303.9. A separate permit will require completion for obtaining a final inspection of this renovation permit.

ELECTRICAL PLANS:

1. Show a smoke alarm in the bedroom and outside of the doorway in the immediate vicinity, R314.3.
2. Show bathroom receptacle outlets with GFCI protection, E3901.6.
3. Show new or extended interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights and smoke detectors with combination type arc-fault circuit interrupters, E3902.16.

INTERNATIONAL ENERGY CONSERVATION CODE:

1. Clarify the wall insulation value (R-60) notation shown on page #2, #6 and #14. Identify the product and installation method.
2. Both standard and high-density R-30 batt insulation requires a space greater than provided with 2” x 6” framing shown on page #3, N1102.1. Identify the products that provide the intended minimum R-30 total value with a 2-layer batt and ridge board system or closed cell foam, R806.5.

If you have any questions, please contact:
Ken Van Karsen
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
07/07/2023 PDSD Application Completeness Express REVIEW COMPLETED