08/16/2023 Bldg Permits - Post Review PENDING ASSIGNMENT
08/16/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0623-05693 (616 N JASMINE PL TUCSON, AZ 85710)
Revision #1 Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Specify and show a continuous Grounding Electrode Conductor to the MSP, IRC E3610.1, NEC 250.64(C) and (D).
2. Show the grounding rods and NG bond in the MSP, IRC E3607.3, E3608.1. (Note: TEP may require a NG bond in the fused disconnect as well).
3. Provide engineer’s stamps on the updated plans, R106.1. (Original plans were stamped).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
07/24/2023 PDSD Application Completeness REVIEW COMPLETED