Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESTAMP - RESIDENTIAL v.1
Permit Number - TC-RES-0623-05686
Review Name: RESTAMP - RESIDENTIAL v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 10/16/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 10/16/2023 | Residential Building | REQUIRES RESUBMIT | Please re-upload the original construction documents attached to the updated site plan. Show the original electrical line for the electrical from the MSP to the shed. Include the following note on the Electrical page. Al receptacle outlets in accessory buildings Shall have ground fault circuit interrupting protection (GFCI), E3902.2. |