Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.1
Permit Number - TC-RES-0526-02703
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/29/2026 | Residential Engineering | APPROVED | |||
| 05/27/2026 | Residential Zoning | APPROVED | |||
| 06/09/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/09/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please address the comments below and re submit. 1. Please show distance from property lines on site plan to confirm fire separation. Also, a roof projection (overhang beyond beam) may not extend closer than 24” to the adjoining (neighboring) property line. Any part of a roof projection extending into the 3-foot fire separation distance from the property line requires not less than one-hour fire-resistive construction on the underside, R302.1 (City of Tucson Amended). 2.Show the HVAC system size accordance with M1401.3, M1601.1. 3.Provide demand calculations in accordance with Manual J standards, M1401.3, M1601.1. 4. Show the return air opening size required by the design conditions, M1602.2.3. 5. Show an individual accessible water supply shut off and water heater for the proposed dwelling unit, P2903.9.1. 6. Show water piping with a developed length of not exceed 100 feet from the source of hot water to the furthest fixture, P2905.3. 7. Show the water heater rating/capacity if proposed as a new unit, P106.1.1. 8. Show location of smoke alarms. 9. Provide the Riser Diagram for the close dwelling and the feeder size to the detached dwelling panel per TEP coordination, NEC 225.30 and E3403. 10. Provide full cut-off FCO style fixtures or provide an Outdoor Lighting Calculation including all exterior fixtures on the property for determining compliance within exterior lighting limits. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3. |
||
| 05/22/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |