Review Details: RESIDENTIAL ADD/ALT v.1
Permit Number - TC-RES-0526-02643
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2026 | Residential Engineering | NOT REQUIRED | |||
| 05/21/2026 | Residential Zoning | NOT REQUIRED | Exterior wall renovations/repairs only - no change to floorplan or building footprint; zoning review not required. | ||
| 05/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/20/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions, please contact PDSD-Permits@tucsonaz.gov Please include full property address on site plan and resubmit after other reviews are complete. Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-re… |
||
| 05/28/2026 | Residential Building - Standard | REQUIRES RESUBMIT | TC-RES-0526-02643 PLAN REVIEW COMMENTS Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions. SCOPE OF REVIEW: The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval. PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance. Place the current 2024 IRC reference code on the plans. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections. Provide a separate response letter addressing each comment with location of change on the plans. Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits SITE PLAN: 1. Show the location of the electrical service panel, R106.1.1. SECTIONS - DETAILS: 1. Provide a landing at the proposed exterior door. A landing must be at least as wide as the door and 36” in the direction of travel, R311.3. 2. Provide a wall section detail for the proposed exterior framed (insulated) wall below the window location with a pressure treated sill including ½” anchor bolts, R403.1.6. 3. Specify water-resistive barrier over the wood-based sheathing, R703.2. 4. Show exterior wood siding, sheathing and wall framing with a 6” clearance above the ground (R317.1 item 5). The weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. ELECTRICAL PLANS: 1. Show a switch-controlled light at each side of outdoor entrances/exits for illuminating the landing and room interior, E3903.3. 2. Altered circuits require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans. OUTDOOR LIGHTING CODE 1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3. If you have any questions, please contact: Kenneth.VanKarsen@tucsonaz.gov City of Tucson Residential Building Safety |
||
| 05/20/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |