Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0526-02553
Parcel: 113103580

Address:
1427 E SPRING ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.3

Permit Number - TC-RES-0526-02553
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/08/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:

1) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67
06/09/2026 Light Residential Building Review (OIP) Express REVIEW COMPLETED electrical reconnect only-no work being done
06/08/2026 PDSD Application Completeness Express REVIEW COMPLETED