Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.3
Permit Number - TC-RES-0526-02553
Review Name: RESIDENTIAL SIMPLE REVIEW v.3
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/09/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/08/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 |
||
| 06/09/2026 | Light Residential Building Review (OIP) Express | REVIEW COMPLETED | electrical reconnect only-no work being done | ||
| 06/08/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |