Permit Number: TC-RES-0526-02534
Parcel: 118200250

Address:
359 W 22ND ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0526-02534
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) Clarify if an A/C unit will be installed. If so, provide a Manual J calculation showing the sizing of the unit to be installed is adequate.
2) Provide a Load Calc. for the electrical including additional load from the new unit. NEC 220 Part III. Include conductors and all supplemental equipment used to supply the new central unit.
3) GFCI Service receptacle must be provided within 25 ft of the HVAC system 210.63