Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0526-02534
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/14/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/14/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Clarify if an A/C unit will be installed. If so, provide a Manual J calculation showing the sizing of the unit to be installed is adequate. 2) Provide a Load Calc. for the electrical including additional load from the new unit. NEC 220 Part III. Include conductors and all supplemental equipment used to supply the new central unit. 3) GFCI Service receptacle must be provided within 25 ft of the HVAC system 210.63 |
||
| 05/14/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |