| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/13/2026 | Addressing Validation | REQUIRES RESUBMIT | If you have questions, please contact PDSD-Permits@tucsonaz.gov Please include full property address on the site plan and resubmit after other reviews are complete. Please specify the unit number. Address must match the address on the permit application. Here are the Step-by-Step instructions on how to resubmit: https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf |
||
| 05/13/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) A Surge Protection Device (SPD) must be identified on the plans. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67 2) Each structure must have their own permit, please submit a change of address request to remove the ADU (Unit 2) and submit an additional trade permit to address the ADU (Unit 2). If the service panels share the same meter, please show this in the next submittal. |
||
| 05/13/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |