Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR REVISION v.1
Permit Number - TC-RES-0526-02485
Review Name: RESIDENTIAL SOLAR REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/28/2026 | Residential Zoning | APPROVED | |||
| 07/24/2026 | Residential Engineering | NOT REQUIRED | |||
| 07/28/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/27/2026 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please show distances of wheel barriers adhering to R330.8.3.3 Protection from Impact. Show spacing and distance from ESS, wheel barriers must be no less than 54" from ESS and spacing between wheel barriers shall not exceed 36". If the manufacturer's installation instructions specify different dimensions, provide the installation instructions demonstrating compliance. |
||
| 07/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |