Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0526-02480
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/12/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) The feeder circuit for this project does not adhere to the IRC requirement for adequately supplying all circuits E3704.5 Based on the information presented, the circuits provided require an 85 A demand with a minimum current carrying conductor size of 4 AWG. Please include a grounded conductor and equipment grounding conductor sized based on NEC requirements. Note: NEC 220 calculations can determine the feeder branch sizing based on the demand. 2) Please verify if each individual outlet circuit need multiple circuits, this may allow for a smaller feeder branch. |
||
| 05/12/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |