Permit Number: TC-RES-0526-02480
Parcel: 11203294B

Address:
2560 E ROSS PL

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0526-02480
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/12/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) The feeder circuit for this project does not adhere to the IRC requirement for adequately supplying all circuits E3704.5 Based on the information presented, the circuits provided require an 85 A demand with a minimum current carrying conductor size of 4 AWG. Please include a grounded conductor and equipment grounding conductor sized based on NEC requirements.
Note: NEC 220 calculations can determine the feeder branch sizing based on the demand.
2) Please verify if each individual outlet circuit need multiple circuits, this may allow for a smaller feeder branch.