Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) Please clarify scope of work, specify if a service panel will be added or replaced. Additional units must be addressed separately to receive separate meters.

If the service panel supplying 100% of the electrical load to a dwelling is installed/replaced, it must adhere to 230.67. A SPD must be listed on the plans, this device must be a Type 1 or 2, UL 1449 Listed, and have a nominal discharge rating of at least 10kA.