| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 07/21/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 07/21/2026 | Residential Building - Standard | REQUIRES RESUBMIT | Please review the comments below and resubmit. 1.Provide a wall section detail showing exterior wall materials with a 6” clearance above the ground (R317.1 item 5). Weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1. 2.Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6. 3.Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Identify the ventilation requirements and insulation types for complying with the condensation control issues. 4.Show location of smoke detectors |
||