Permit Number: TC-RES-0526-02321
Parcel: 133060030

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.3

Permit Number - TC-RES-0526-02321
Review Name: RESIDENTIAL ADD/ALT v.3
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
07/21/2026 Residential Building - Standard REQUIRES RESUBMIT Please review the comments below and resubmit.
1.Provide a wall section detail showing exterior wall materials with a 6” clearance above the ground (R317.1 item 5). Weep screed may extend with a minimum clearance 4” above grade or 2” above paved areas, R703.7.2.1.
2.Provide a wall section detail with (#4 rebar) reinforced 12” x 12” reinforced foundations for anchoring exterior framed (insulated) walls with pressure treated sills including ½” anchor bolts with 7” embedment, R403.1.6.
3.Clarify the placement of ceiling/roof insulation for determining the need for attic ventilation, R806. Attic space outside of the thermal barrier requires a ventilation calculation for showing the attic vent opening size using 1 to 150 of attic area in compliance with R806.2 or an unvented roof assembly requires an air-impermeable rigid insulation material with a minimum R-5 value applied correctly to either side of the roof sheathing, R806.5. Identify the ventilation requirements and insulation types for complying with the condensation control issues.
4.Show location of smoke detectors
07/17/2026 PDSD Application Completeness Express REVIEW COMPLETED