Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0526-02305
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/05/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/05/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please clarify if you will use a NEMA Outlet or if the unit will be hardwired 2) Site plan does not show location of installation will be protected from impact. Show the location of the EV charger is protected from vehicular impact. E3404.10, 110.27(B) 3) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices) 625.54 4) Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E404.14.1 |
||
| 05/04/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |