Permit Number: TC-RES-0526-02304
Parcel: 123041040

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0526-02304
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/12/2026 Residential Zoning APPROVED
05/07/2026 Residential Engineering NOT REQUIRED
05/19/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/19/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0526-02304
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Provide a separate response letter addressing each comment with location of change on the plans.

ELECTRICAL PLANS:

1. Show a single feeder or branch circuit to the accessory (detached) building, NEC 225.30.
2. Show the location and ampacity of a panelboard for the 3 proposed branch circuits, E3405.2.

OUTDOOR LIGHTING CODE

1. Show full cutoff fixtures were located within 25 feet from the property line OLC 401.3.3.