Permit Review Detail
Review Status: In Review
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0525-02704
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: In Review
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/27/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/27/2025 | Site Engineering Express | PENDING ASSIGNMENT | |||
| 05/27/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Permit Review TC-RES-0525-02704 (918 W CALLE FRANCITA TUCSON, AZ 85706) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response letter to each of the notated items indicating action taken. For questions: Building_Official@tucsonaz.gov 1. Show exact location of the panel to be upgraded. The location marked on the site plan appears to be inside of the building. TEP usually requires the service panel on the property at the closest building to the service transformer. You may need to work with TEP to provide a safe and code compliant location for the service equipment. 2. If this is not the case and the meter/panel is in fact not inside of the building please clearly provide the exact location on your site plan. 3. Aerial views of the property show the overhead service conductors will be passing over the roof. The overhead service conductor over the structure requires an 8’ clearance above the roof, E3604.2.1. The 8’ clearance is required to be maintained for a distance of 3’ from the edge of the roof. Show a mast height necessary to achieve this clearance. Check with TEP customer service for service line options. https://www.tep.com/electric-service-requirements |
||
| 05/27/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |