Permit Number: TC-RES-0525-02550
Parcel: 112052670

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0525-02550
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/14/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/14/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0525-02550 (2202 E FLORENCE DR TUCSON, AZ 85719) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC).
1. Gas Lines- Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. Sections of the pipe from the shutoff valve back to the meter are undersized and need to be 1 1/4 from the meter to the shutoff valve. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/permits/residential-permits/gas_handout_2018_irc_2019.2.4.pdf