Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0525-02533
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/13/2025 | Site Engineering - Standard | NOT REQUIRED | |||
| 06/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/04/2025 | Light Residential Building Review (OIP) - Standard | REQUIRES RESUBMIT | Permit Review TC-RES-0525-02533 (10589 E FELTLEAF WILLOW TR TUCSON, AZ 85747). Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Show interconnection at the PV panel in compliance with NEC 705.12(B). 2. Verify the existing inverter model number to the listing on the plans and adjust accordingly. Building_official@tucsonaz.gov |
||
| 05/13/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |