Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0525-02445
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/13/2025 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/13/2025 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | ACTIVITY NO. TC-RES-0525-02445 ADDRESS/PARCEL: (8072 S CARBURY WY TUCSON, AZ 85747) Submit your revised drawings along with a detailed response letter, which states how all Building Review Section comments were addressed. The submitted documents were incomplete and a thorough plan review could not be performed. Please be aware, new comments may arise with the next review. Review will not proceed without the response letter. COMMENTS: 1. Please correct the values listed below in Manual J (based on the IRC and the City of Tucson Amendments to the 2018 IRC) a. Outdoor Dry Bulb Temp: i. 105 +/- 2 degrees ii. 35 +/- 2 degrees 2. The assessor has the square footage at 1427 sq ft and you have it listed as 1892 sq ft. Please list the correct square footage and adjust your Manual J calculation accordingly. 3. Based on the Manual J provided, the HVAC unit appears to be undersized. We want to compare the sensible capacity of the unit with the sensible load from the home. Please show that the two are within +/- 6000 Btuh. Please submit the extended rating table for the unit as well. 4. Please resubmit |
||
| 05/12/2025 | PDSD Application Completeness Express | REVIEW COMPLETED |