Permit Number: TC-RES-0525-02316
Parcel: 13012291B

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0525-02316
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/07/2025 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/07/2025 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT Permit Review TC-RES-0525-02316 (3559 E ELLINGTON PL TUCSON, AZ 85713)

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide an updated Plan and a written response letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response letter addressing the comments below maybe be delayed until the response letter is received.

1. Sizing the pipe based on the length from the meter to the farthest attached appliance and max total demand of all attached appliances using Table G2413.4(1) (Metallic Pipe). For the given length, 80’, and total demand, 135,000 BTUs, Pipe size from meter to the farthest attached appliance is undersized, must be a minimum of 1'' per Table G2413.4(1). See drawing for markups.

2. Gas template should note and specify all piping materials (Black Iron, Gas line PEX, etc.), G2412.9.
05/07/2025 PDSD Application Completeness Express REVIEW COMPLETED