Review Date Reviewer's Name Type of Review Description Status Comments
06/18/2024 Site Engineering NOT REQUIRED
06/18/2024 Bldg Permits - Post Review PENDING ASSIGNMENT
06/12/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0524-03138 (202 E GLENN ST TUCSON, AZ 85705)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. TEP does not allow 2 DG meters, the two systems will need to be combined to go through one DG meter. Check with TEP customer service for interconnection requirements. https://www.tep.com/electric-service-requirements
2. There is no record of a 225A rated Main service panel. Provide documentation showing the service panel bus is rated at 225A.
3. Include the existing solar system in the 120% bus calculations. This is required for verification of interconnection and conductor and OCPD sizing compliance. 690.8, 705.12.
4. For wind uplift use 115 mph in 3sec gust, Table R301.2(1). https://www.tucsonaz.gov/files/sharedassets/public/pdsd/documents/building-code/2018_-_irc_amendments.pdf
5. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems


Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov