Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0524-03050
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
06/18/2024 | Site Engineering | NOT REQUIRED | |||
06/18/2024 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/18/2024 | Historic | REQUIRES RESUBMIT | HPZ minor review was completed. Approval letter signed. Applicant may proceed to permitting. No further HPZ review required. HPZ-Completed Contact: Michael.Taku@tucsonaz.gov NOTE: Previous comments dated 6/14/2024, were in error and not intended for this application. Please, ignore. Focus on these revised comments. Please submit all the same materials under the Historic sub-record. Once you log into TDC Online, go to the My Work tab, and then go to Plans (not Permits). Under Plans there should be the Historic sub-record which I have opened under the TC permit number, and this is where the materials are submitted. Given that the application is for solar panels, it will be a Minor review. On page 2 of this document under Minor review in the table are all the items that you will need for the historic minor review. In addition to documents submitted for the permit, please add a project description/narrative; color photo of the house showing where the panels will be located; AZ Historic Property inventory Form; and drawing to indicate the distance from the roof to panels. Once submitted the system will generate an SD #. Staff will then contact you about the next steps including invoicing and payment of review fee. Once fee are paid, a minor review will be scheduled. See link below for steps on resubmitting. https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf I am also attaching a flow chart that should help you understand the process. If you have any questions, contact Michael Taku at Michael.Taku@tucsonaz.gov |
||
06/06/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). 1. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability for 115 MPH, and provide an engineer’s calculation, and sealed design, R301.1, R324.4. 2. Provide complete roof framing information for determining load carrying capacity for the roof structure. Show all load bearing locations. Demonstrate the ability for supporting the existing and additional dead load, and provide an engineer’s calculation, design, and seal for verifying the truss load carrying capacity. R324.4 Equipment shall be positively attached to the roof structure with a minimum of one connection per 10 sf of equipment (minimum of two connections per piece of equipment). Point loads exceeding 40 lbs shall require a structural load analysis by licensed Arizona engineer. R106.1 and R301.1.3 Building_official@tucsonaz.gov |
||
06/07/2024 | Site Zoning | REQUIRES RESUBMIT | ZONING REVIEW TRANSMITTAL FROM: Wyatt Berger Lead Planner PROJECT: TC-RES-0524-03050 5396 East Francisco Loop – HR-1 5.74kW roof-mounted photovoltaic system (1st Review) TRANSMITTAL DATE: June 7, 2024 1. The site is in the Fort Lowell Historic Preservation Zone (HPZ). The proposal requires minor HPZ review in accordance with Tucson Unified Development Code (UDC) 5.8.8.C. The Historic and Special Districts Application Instructions can be found at: https://www.tucsonaz.gov/files/sharedassets/public/v/3/pdsd/documents/submission-documents/special_districts_application_instructions_7.18.23.pdf. The minor HPZ review process is a separate submittal and shall be applied for as a sub-record of TC-RES-0524-03050. Zoning cannot approve TC-RES-0524-03050 until the minor HPZ review process is completed. If you have any questions about this transmittal, contact me at Wyatt.Berger@tucsonaz.gov or at 520-837-4951. RESUBMITTAL OF THE FOLLOWING IS REQUIRED: A revised plan set as well as a comment response letter. To resubmit, visit the Tucson Development Center Online at https://tdc-online.tucsonaz.gov/#/home. The instructions for resubmittal can be found at https://www.tucsonaz.gov/files/sharedassets/public/v/1/pdsd/documents/tdc-faq/new-pdfs/revisions-and-resubmittals.pdf. |
||
05/20/2024 | PDSD Application Completeness | REVIEW COMPLETED |