Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0524-02996
Parcel: 120051530

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0524-02996
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/13/2024 Site Engineering NOT REQUIRED
06/13/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/05/2024 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0524-02996 (909 W MISSOURI ST TUCSON, AZ 85714)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC).

1. Conductor Tag ID C0 is undersized for the given 60A Meter Socket Adapter breaker. Conductors shall be protected with OCPD’s having a rating not exceeding the allowable ampacity of the conductor, IRC E3705.5, reference NEC 310.15, 240.4.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/16/2024 PDSD Application Completeness Express REVIEW COMPLETED