Permit Number: TC-RES-0524-02852
Parcel: 125050820

Address:
2409 E 5TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0524-02852
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/10/2024 Site Engineering NOT REQUIRED
06/10/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/23/2024 Residential Building REQUIRES RESUBMIT Provide a complete construction plan set showing 2018 IRC compliance after DDO approval.

Provide an engineer’s calculation, design, and seal for a performance design when altering an existing structure for accepting new bearing loads, R301.1.
06/06/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review Section

PROJECT: TC-RES-0524-02852
2409 E. 5th St. – R-1
Residential addition (1st Review)

TRANSMITTAL DATE: June 6, 2024

COMMENTS: Resubmit revised drawings along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence is a permitted use in this zone (Table 4.8-2) subject to Use Specific Standards 4.9.7.B.5 – 9

1. The street frontage listed, “GREATER OF 20’-0” OR 1-1/2 HEIGHT” is not correct. Review UDC Article 6.4.5.C.1.a, and correct the front street perimeter yard setback.

2. The plot plan shall be drawn at an engineering scale, i.e. 1” = 10’, 1” = 20’.

COMMENTS: the following comments are relative to an application for a Design Development Option (DDO) (UDC 3.11.1).

Perimeter yard setbacks are based on a wall height measurement from design grade to the highest point of the exterior wall, top of parapet, UDC Article 6.4.5.B & Figure 6.4.5-A. As wall height dimensions to the top of parapet, where the parapet steps down Zoning has used the dimension of 23’-8” that was provided to the top of parapet at its highest point to determine required perimeter yard setbacks.

1 The minimum setback is the greater of six (6) feet, or two-thirds (2/3) the height of the structure’s wall facing each interior property line (Table 6.3-2.A). Based on a wall height of 23’-8” the required interior perimeter yard setback from the proposed 2-story addition to the north, east and west property line is 15’-10”. Proposed perimeter yard setback from the north wall of 2-story addition to the north property line appears to be 13’-8” but the dimension is cutoff and not readable. Proposed setback from the 2-story addition to the east property line is 7’-4” and to the west property line is 8’-9”.

2 Based on a wall height of 13’-4” the required perimeter yard setback from the north wall of the proposed 1-story garage addition to the north property line is 8’-11”, propose setback from the 1-story garage addition is 3’-6”.

The Unified Development Code (UDC) can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Codes/Zoning-Code.

A Design Development Option (DDO) must be submitted and approved to reduce the required setback. DDO application and requirements can be found at: https://www.tucsonaz.gov/Departments/Planning-Development-Services/Planning-Zoning-Applications/Zoning-Administration. If you have questions about the DDO application or process please contact Wyatt Berger at Wyatt.Berger@tucsonaz.gov or Georgia Pennington at Georgia.Pennington@tucsonaz.gov.

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov.
05/13/2024 PDSD Application Completeness Express REVIEW COMPLETED