Permit Number: TC-RES-0524-02750
Parcel: 127122110

Address:
5746 E 8TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.2

Permit Number - TC-RES-0524-02750
Review Name: RESIDENTIAL NEW DWELLING v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
07/08/2024 Site Engineering NOT REQUIRED
07/08/2024 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/24/2024 Residential Building REQUIRES RESUBMIT TC-RES-0524-02750
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2018 International Residential Code and 2018 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2018 IRC code compliance. The plans require sufficient detail for demonstrating an awareness of minimum building code compliance for passing all progress inspections.

Provide a response letter on separate file with submitting the updated construction plan set.

FLOOR PLAN:

1. Clarify if the wall separating the garage extension and laundry is existing or proposed, R106.1.
2. Show the door from the garage to laundry room with a 20-minute fire rating (or 1-3/8” solid core) with self-closing and self-latching provision, R302.5.1.

STRUCTURAL PLANS:

1. Provide a complete plan set showing materials and fastener sizes with 2018 IRC prescriptive compliance or provide an Arizona professional stamped plan set showing performance compliance with wind loading conditions, R301.1.

2. The proposed Patio Cover may be sited within the 3’ fire separation distance from a property line. Show compliance with R302.1 (City of Tucson Amended) by providing a wall with one-hour rated materials prescribed in IBC Table 721.1(2), Items 15-1.1 to 16-1.3, R106.1 or remove any structure closer than 3 feet to the property line.

MECHANICAL PLANS:

1. Show a dryer vent size and location for venting to exterior, M1501.

ELECTRICAL PLANS:

1. Garage Receptacle Location: a 20 AMP receptacle outlet is required at each vehicle bay not more than 5.5 feet above the floor, E3901.9.
2. Show the Clothes Washer with a 20 AMP GFCI receptacle require readily accessible protection typically from an upstream device, E3902.9 & 10.

If you have any questions, please contact:
PDSD-Residential@tucsonaz.gov
City of Tucson Residential Plan Review

Submit a corrected plan set at https://www.tucsonaz.gov/Departments/Planning-Development-Services
07/03/2024 Site Zoning REQUIRES RESUBMIT FROM: PDSD Zoning Review

PROJECT: TC-RES-0524-02750
5746 E 8TH ST. – R-1
Garage Extension and Enclose Laundry Room (2nd Review)

TRANSMITTAL DATE: July 3, 2024

Resubmit revised drawings and any redlined plans along with a detailed response letter, which states how all Zoning Review Section comments were addressed.

This site is located in the R-1 zone (UDC 4.7.8). A single-family residence (SFR) is a permitted use in this zone (Table 4.8-2). See Use-Specific Standards 4.9.7.B.5 – 9.

1. The permit application states ”Garage Extension” but the plot plan shows a “CARPORT” and “ADDITION”.

2. Provide a dimension from the centerline of 8th St. to the face of curb, where pavement meets the concrete curb, and from face of curb to the north property line. Contact COT Transportation & Mobility, Maps and Records. Based on Clara Vista final plat the distance from centerline of 8th to the property line is 25’.

3. The lot coverage calculation is not correct. Per UDC Article 6.4.3 Roofed areas, porches, open on at least one side, pools and slabs are not included in the calculation.

4. The “REAR 10’” setback listed on the plot plan is not correct. Per UDC Table 6.3-2.A, R-1 Zone, Residential Use to a Residential Zone the setback is 6’-0” or 2/3 (H), height of the exterior, greater of the two>

If you have any questions about this transmittal, please contact Zone1.desk@tucsonaz.gov
06/12/2024 PDSD Application Completeness Express REVIEW COMPLETED