Review Details: RESIDENTIAL SOLAR v.2
Permit Number - TC-RES-0524-02655
Review Name: RESIDENTIAL SOLAR v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/04/2024 | Site Engineering | NOT REQUIRED | |||
| 06/04/2024 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/09/2024 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0524-02655 (626 W 41ST ST Unit:UNIT 1 TUCSON, AZ 85713) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC), 2017 National Electrical Code (NEC). 1. OCPD for copper conductor may not exceed 30A for #10 rating as required by E3705.5.3 and NEC 240.4(D)(small conductors). Conductor C-1 is undersized for the given OCPD. 2. Provide a Grounding Electrode System at the detached structure per NEC 690.47. 3. Verify the correct unit number is being used. Pima County appears to show this structure as UNIT 2, not UNIT 1. Verify with TEP and Pima County to ensure that the electrical clearance will be accepted by TEP. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||