Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0523-05579
Parcel: 140375420

Address:
5981 E TERCEL DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0523-05579
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/26/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/26/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0523-05579 (5981 E TERCEL DR TUCSON, AZ 85756)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

1. Provide complete roof framing information for determining load carrying capacity for the roof structure, showing the location and size of beams, headers, truss’, and rafters for supporting live and dead structural loads, R804. Show racking equipment and all load bearing locations. Demonstrate the ability for supporting the existing and additional dead load, or provide an engineer’s calculation, design and seal for verifying the truss load carrying capacity. R324.4
2. Provide a lag-bolt connection up-lift calculation demonstrating the wind load supporting capability, or provide an engineer’s calculation, and sealed design, R301.1, R324.4. An IRC PV roof uplift calculator (XLS) is available on Pima County’s website. https://www.pima.gov/1069/Solar-Wind-Systems
3. All New equipment, including Panels, Racking systems, Inverters etc.. Shall be UL listed. R324.3
4. Provide manufacturer specification sheets for all collector panels, inverters, mounting hardware, power optimizers etc. R324.3
Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/06/2023 PDSD Application Completeness Express REVIEW COMPLETED