Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SOLAR v.1
Permit Number - TC-RES-0523-05479
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 06/22/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 06/22/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0523-05479 (7601 E LAKESIDE DR TUCSON, AZ 85730) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received. Code reference, 2018 International Residential Code (IRC). • Provide electrical load calculations for determining the service panel size, E3602.2. • Provide a Main Service Panel schedule showing the MSP manufacturer, size and total number of shutoff switches, E3404.11, E3706.2. • E3601.7 Maximum number of disconnects. The service disconnecting means shall consist of not more than six switches or six sets of circuit breakers mounted in a single enclosure or in a group of separate enclosures. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 06/01/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |