Permit Number: TC-RES-0523-05479
Parcel: 136341800

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SOLAR v.1

Permit Number - TC-RES-0523-05479
Review Name: RESIDENTIAL SOLAR v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
06/22/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/22/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0523-05479 (7601 E LAKESIDE DR TUCSON, AZ 85730)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

• Provide electrical load calculations for determining the service panel size, E3602.2.
• Provide a Main Service Panel schedule showing the MSP manufacturer, size and total number of shutoff switches, E3404.11, E3706.2.
• E3601.7 Maximum number of disconnects. The service disconnecting means shall consist of not more than six switches or six sets of circuit breakers mounted in a single enclosure or in a group of separate enclosures.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
06/01/2023 PDSD Application Completeness Express REVIEW COMPLETED