05/24/2023 Light Residential Building Review (OIP) REQUIRES RESUBMIT Permit Review TC-RES-0523-05380 (11420 E VAIL CREST DR TUCSON, AZ 85747)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

1. Hooking in a new gas appliance into the existing gas line may require the upsizing of the main line out of the meter. Provide the following information for code verification.
a. Longest length, measured from the meter to the farthest attached appliance, G2413.4.1. This length is used in the following tables to select the correct pipe sizes. (Use the next largest length row that is greater than the longest length measurement. )
b. The individual demand of each attached appliance and total demand. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe). (100,000 BTUh = 100 Cubic Feet of Gas per Hour).

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov