Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL NEW DWELLING v.1
Permit Number - TC-RES-0523-05147
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
---|---|---|---|---|---|
05/30/2023 | Site Zoning | APPROVED | |||
05/19/2023 | Site Engineering | NOT REQUIRED | |||
06/16/2023 | Bldg Permits - Post Review | PENDING ASSIGNMENT | |||
06/16/2023 | Residential Building | REQUIRES RESUBMIT | Please respond to the following: 1. Not less than one receptacle outlet in addition to any provided for specific equipment shall be installed in each vehicle bay not more than 5.5 feet above the floor in attached garages & detached garages. IRC E3901.9 2. Garage and accessory building receptacles shall have ground-fault circuit-interrupter protection. Per IRC E3902.2 3. Openings between the garage and residence shall be equipped with self-closing, solid-core, 1-3/8” door or 20 minute rated door. R302.5.1 4. Not less than 1/2 inch gypsum board or equivalent applied to the garage side as dwelling/garage fire separation per IRC 2012 R302.6 & Table R302.6 5. Garage lights and switch(es) - show them on the electrical drawing. 6. Identify the breakers being used to power the garage. 7. Show power for the roll up doors. 8. Submit an electrical drawing depicting all of the items above. |
||
05/15/2023 | Fire New Construction | REVIEW COMPLETED | |||
05/15/2023 | PDSD Application Completeness | REVIEW COMPLETED |