Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1
Permit Number - TC-RES-0523-05056
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/12/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/12/2023 | Residential Building | REQUIRES RESUBMIT | Permit Review TC-RES-0523-05056 (940 N CITADEL AV TUCSON, AZ 85748) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Code reference, 2018 International Residential Code (IRC). SITE PLAN: 1. Indicate the location and size of buildings, utility meters and lines, Show the building in relationship to the street, R106.1.1. https://www.tucsonaz.gov/files/pdsd/forms/Residential_Plot_Plan_Requirements.pdf 2. Indicate above ground line, or below ground line. Show the new line’s connection all the way to the TEP power source. 3. Provide an electrical riser diagram, E3403. Notate the grounding and bonding method, E3607. Metallic gas lines must be bonded and not be used as the primary grounding method, E3608. 4. Provide a Main Service Panel with a clear working space of 30” wide x 36” deep, E3405.2. 5. Provide a MSP schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/11/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |