Permit Number: TC-RES-0523-05031
Parcel: 12217417B

Review Status: Requires Resubmit

Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.1

Permit Number - TC-RES-0523-05031
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/16/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/16/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0523-05031 (1620 N CAMILLA BL TUCSON, AZ 85716)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken.
Code reference, 2018 International Residential Code (IRC).

Addition of a new gas appliance requires a complete gas plan:
1. Provide gas piping plan. Show connection, lengths and sizes, from gas meter to all gas appliances. See https://www.tucsonaz.gov/files/pdsd/permits/GAS_HANDOUT_2018_IRC_2019.2.4.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Gas_Piping_Template.pdf
https://www.tucsonaz.gov/files/pdsd/permits/Sample_Gas_Template_0.pdf
2. Provide total demand from all appliances.
3. Use G2413.4.1 and G2413.4.2 to determine the required developed length to be used in sizing tables.
a. G2413.4.1 Longest length method: Length is from Meter to the furthest connected appliance. Use this same length to determine all pipe sizes.
b. G2413.4.2 Branch length method: Branch length is from Meter to the furthest connected appliance on given branch. Any unsized branches, use length from Meter to the furthest appliance.
4. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. (Table G2413.4(7) Polyethylene Plastic Pipe).
5. Show a GFCI receptacle outlet on the same level within 25’ of new exterior HVAC equipment, E3901.12.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov