Permit Number: TC-RES-0523-04906
Parcel: 103110010

Review Status: Requires Resubmit

Review Details: RESIDENTIAL NEW DWELLING v.1

Permit Number - TC-RES-0523-04906
Review Name: RESIDENTIAL NEW DWELLING v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/17/2023 Site Zoning NOT REQUIRED
06/08/2023 Bldg Permits - Post Review Express PENDING ASSIGNMENT
06/08/2023 Residential Building REQUIRES RESUBMIT Permit Review TC-RES-0523-04906 (3340 N GRANNEN RD TUCSON, AZ 85745)
Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Resubmitted plans that do not contain a written response Letter addressing each of the notated items indicating action taken, may be delayed until response letter is received.
Code reference, 2018 International Residential Code (IRC).

Electrical Review:
1. Provide a panel schedule showing panel size, circuit numbers, ampacity, wire size and general description, E3404.13 & E3706.2. Provide a panel schedule showing wire size of each circuit or notate the wire size for each protection rating, E3702.2.
2. Cross reference all electrical outlets, lights, receptacles, etc, (Sheet 5.0) to the corresponding circuit number in the panel schedule, 3606.3.

Framing/Structural Review:
3. On sheet 3.0, details 3 and 4, show the anchor bolts with a minimum 7” embedment into the existing footing, R403.1.6.
4. On sheet 3.0, detail 4, correct the 4x6 post size to be consistent with sizes in the Kitchen Foundation Plan and Kitchen Framing Plan.
5. Provide the total span length for both the 5 1/8”x13 ½” glulam beam and the (2)2x10/(3)2x8 header, R301.1.

Mechanical Review:
6. Show the kitchen exhaust fan minimum 100 CFM rating, M1505.
7. Show the 24x8 SAR is in accordance with Manual D calculations, M1601.1.

Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov
05/04/2023 PDSD Application Completeness Express REVIEW COMPLETED
05/04/2023 Site Engineering REVIEW COMPLETED