Permit Review Detail
Review Status: Requires Resubmit
Review Details: COMMERCIAL PDSD SIMPLE REVIEW v.2
Permit Number - TC-RES-0523-04896
Review Name: COMMERCIAL PDSD SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/20/2023 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/20/2023 | Light Residential Building Review (OIP) | REQUIRES RESUBMIT | Permit Review TC-RES-0523-04896 (9040 E WRIGHTSTOWN RD TUCSON, AZ 85715) Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide updated Plans/calculations and a written response Letter to each of the notated items indicating action taken. Code reference, 2018 International Residential Code (IRC). 1. Given the develop length of 40’ and the total demand of 185 CF/H, 1” pipe size is required. 2. Use G2413.4.1 to determine the required developed length to be used in sizing tables. a. Length is measured from the Meter to the furthest connected appliance. The provided length on your plans = 40’. 3. Use Table G2413.4(1) (Metallic Pipe) to calculate correct required pipe sizes. Contact Jeremy Hamblin with any questions: Jeremy.hamblin@tucsonaz.gov |
||
| 05/18/2023 | PDSD Application Completeness Express | REVIEW COMPLETED |