Permit Number: TC-RES-0426-02118
Parcel: 113082510

Review Status: Requires Resubmit

Review Details: RESIDENTIAL POOL v.1

Permit Number - TC-RES-0426-02118
Review Name: RESIDENTIAL POOL v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Residential Zoning APPROVED
04/28/2026 Site Engineering NOT REQUIRED
05/06/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/06/2026 Residential Building REQUIRES RESUBMIT ACTIVITY NO. TC-RES-0326-01470
PROJECT: RESIDENTIAL POOL
ADDRESS/PARCEL: 2918 N TYNDALL AVE, UNIT 2


Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed.

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Swimming Pool and Spa Code, 2024 International Residential Code and 2024 International Energy Conservation Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions and concerns before permit approval.

If you have any questions about these comments, I can be reached at Matthew.Carlton@tucsonaz.gov


COMMENTS:
1. The Pool Engineering Letter must state Unit 2 on it.
2. Show the equipment on the site plan.
3. Show the electrical run from main panel to equipment on the site plan.
4. Show the distance from the water’s edge to the existing west block wall on the site plan
5. Show the distance between the water’s edge and all overhead electrical lines on the site plan – see power pole located at the SE corner of the property lines. There must be at least a 10’ distance between those.
6. Include the electrical run on the construction plan; TBD is not an actual dimension
7. Show plumbing runs on construction plan
There may be more comments upon resubmittal.

Please upload your revised plans to TDC-Online with a revision letter outlining what has been revised on the doc set.

Resubmittals will not be accepted without the revision letter that answers all of the above comments.
04/24/2026 PDSD Application Completeness Express REVIEW COMPLETED