Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Permit Number - TC-RES-0426-02052
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/15/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) The scope of this project includes an H-Frame and this is not applicable in a trade permit as the appropriate inspections are not included, revise plans to exclude an H-Frame or resubmit as a Res. Solar permit. Please email me in regard to this project for a potential solution or next steps. 2) Please provide the required permanent field marking in accordance with NEC 705.12(B)(3). The service equipment shall be clearly labeled "WARNING: EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT PROTECTION DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR." 3) Show protection from corrosion for circuit A, EMT underground adherence to 358.10(B)(1). |
||
| 05/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |