Permit Number: TC-RES-0426-02052
Parcel: 116024770

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.1

Permit Number - TC-RES-0426-02052
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/15/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) The scope of this project includes an H-Frame and this is not applicable in a trade permit as the appropriate inspections are not included, revise plans to exclude an H-Frame or resubmit as a Res. Solar permit. Please email me in regard to this project for a potential solution or next steps.

2) Please provide the required permanent field marking in accordance with NEC 705.12(B)(3). The service equipment shall be clearly labeled "WARNING: EQUIPMENT FED BY MULTIPLE SOURCES. TOTAL RATING OF ALL OVERCURRENT PROTECTION DEVICE SHALL NOT EXCEED AMPACITY OF BUSBAR."

3) Show protection from corrosion for circuit A, EMT underground adherence to 358.10(B)(1).
05/15/2026 PDSD Application Completeness Express REVIEW COMPLETED