Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Permit Number - TC-RES-0426-02051
Review Name: RESIDENTIAL SIMPLE REVIEW REVISION v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 05/08/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 05/08/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Site plan and Aerial do not match, please match the plans to indicate the location of ESS and electrical equipment location. 2) Provide fire detection within the garage where the Energy Storage System (ESS) is proposed to be installed. R330.7, areas containing ESS installed in attached garages shall be provided with smoke alarms or heat detectors installed in accordance with Section R310, and the plans shall clearly indicate the location of the required device |
||
| 05/08/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |