Permit Number: TC-RES-0426-01984
Parcel: 107051080

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.2

Permit Number - TC-RES-0426-01984
Review Name: RESIDENTIAL ADD/ALT v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
05/04/2026 Residential Engineering NOT REQUIRED
05/06/2026 Residential Zoning NOT REQUIRED Interior renovations/repairs only - no change to floorplan or building footprint; zoning review not required.
05/12/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
05/12/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0426-01984
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. Provide a separate Comment Response Letter when submitting updated plans. Facilitate a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code and 2018 International Energy Conservation Code. The 2024 International Energy Conservation Code takes effect July 1st. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance. The plans require sufficient detail for demonstrating minimum building code compliance for passing all progress inspections.

Provide all plan sheets into a single PDF file.

Provide a separate response letter addressing each comment with location of change on the plans.

Provide a clear and concise construction plan set. Sample drawings are available for understanding details. Sample plans at https://www.tucsonaz.gov/Departments/Planning-Development-Services/Permits/Residential-Permits

ELECTRICAL PLANS:

1. Show the location of the electric panel, E3405.2.
2. Provide a panel schedule showing the required branch circuit ampacity, E3601.6.1 & E3706.2. Some locations require 20 Amp circuits.
3. Show receptacle outlets at wall spaces 2’ or more with no wall point (exclude door openings) more than 6’ from a receptacle outlet, E3901.2.
4. Show 2O AMP small appliance circuits at the kitchen countertop receptacle outlets, E3703.2 and E3901.3.
5. Show Bathroom receptacles with a separate 20 AMP dedicated circuit, E3703.4 and E3901.6.
6. Show at least one wall switch controlled light or outlet in bathrooms, hallways, stairways, attached garages, outdoor entrances or exits and all habitable rooms, E3903.3.
7. Interior 15A & 20A circuits serving outlet locations (except garage, kitchen, and bathrooms) including receptacles, lights, and smoke detectors require combination type arc-fault circuit interrupters, E3902.16. Add notation to plans.

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Building Safety
05/04/2026 PDSD Application Completeness Express REVIEW COMPLETED