Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit Number: TC-RES-0426-01881
Parcel: 127031840

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0426-01881
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/15/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) Please resubmit and provide a site plan or an aerial (from above) photograph with the address. Be sure to show the proposed location of the water heater, this applies even if the location will remain the same.
1) Provide a Manual J calculation showing the sizing of the unit to be installed is adequate for the designated area. Additionally, provide the size of the existing HVAC unit.
3) Provide a please provide a Load Calc. for the service panel for the added load from the new unit. NEC 220 Part III
04/15/2026 PDSD Application Completeness Express REVIEW COMPLETED