Permit Number - TC-RES-0426-01881
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/15/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please resubmit and provide a site plan or an aerial (from above) photograph with the address. Be sure to show the proposed location of the water heater, this applies even if the location will remain the same. 1) Provide a Manual J calculation showing the sizing of the unit to be installed is adequate for the designated area. Additionally, provide the size of the existing HVAC unit. 3) Provide a please provide a Load Calc. for the service panel for the added load from the new unit. NEC 220 Part III |
||