Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0426-01872
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/15/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/15/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) Please provide a clean site plan showing the location of the service panel to be replaced ONLY. If any additional equipment related to the PV will be installed please indicate the equipment, no all equipment to be reinstalled is applicable as a trade. More comments may be forthcoming. 2) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67 3) Provide the PV labels that will be reinstated on the Service panel |
||
| 04/15/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |