Permit Number: TC-RES-0426-01872
Parcel: 122030320

Address:
4502 E SENECA ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0426-01872
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/15/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/15/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) Please provide a clean site plan showing the location of the service panel to be replaced ONLY. If any additional equipment related to the PV will be installed please indicate the equipment, no all equipment to be reinstalled is applicable as a trade. More comments may be forthcoming.

2) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67

3) Provide the PV labels that will be reinstated on the Service panel
04/15/2026 PDSD Application Completeness Express REVIEW COMPLETED