Review Details: RESIDENTIAL SOLAR REVISION v.1

Permit Number - TC-RES-0426-01835
Review Name: RESIDENTIAL SOLAR REVISION v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
08/13/2026 Residential Zoning APPROVED
08/25/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
08/25/2026 Light Residential Building Review (OIP) - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov
Please resubmit addressing the following comment:
1) The SPD provided Eaton BRPSURGE has a 3 kA nominal discharge rating, this device does not comply with the requirement in E3606.5 or 230.67 nor match PV4 nor PV5 equipment description. Please provide the spec sheet of the SPD to be install that is compliant, SPD must have a nominal discharge current rating not less than 10kA, be UL 1449, and be Type 1 or Type 2. 230.67