Review Status: Requires Resubmit
Review Details: RESIDENTIAL ADD/ALT v.2
Permit Number - TC-RES-0426-01823
Review Name: RESIDENTIAL ADD/ALT v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/27/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/27/2026 | Residential Building - Standard | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) Please resubmit and provide an updated site plan or an aerial (from above) photograph with the address. Be sure to show the proposed location of the service panel and A/C to be installed, this applies even if the location will remain the same. 2) per email with applicant A/C unit will be installed. Provide a Manual J calculation showing the sizing of the unit to be installed is adequate 3) Provide a Load Calc. for the service panel for the added load from the new unit. NEC 220 Part III |
||
| 04/27/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |