Review Date Reviewer's Name Type of Review Description Status Comments
04/27/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/27/2026 Residential Building - Standard REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) Please resubmit and provide an updated site plan or an aerial (from above) photograph with the address. Be sure to show the proposed location of the service panel and A/C to be installed, this applies even if the location will remain the same.
2) per email with applicant A/C unit will be installed. Provide a Manual J calculation showing the sizing of the unit to be installed is adequate
3) Provide a Load Calc. for the service panel for the added load from the new unit. NEC 220 Part III