Permit Number: TC-RES-0426-01789
Parcel: 130083350

Address:
3402 E 27TH ST

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0426-01789
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/10/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/10/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comment:
1) Clarify if an A/C unit will be installed along with the electrical circuit. If so, provide a Manual J calculation showing the sizing of the unit to be installed is adequate.
2) Clarify if these are conductors that will replace existing or if this will be a completely new load. If new, provide a panel schedule using NEC 220 to show this added load can adequately be supplied by the existing service panel.
04/10/2026 PDSD Application Completeness Express REVIEW COMPLETED