Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0426-01789
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/10/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/10/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comment: 1) Clarify if an A/C unit will be installed along with the electrical circuit. If so, provide a Manual J calculation showing the sizing of the unit to be installed is adequate. 2) Clarify if these are conductors that will replace existing or if this will be a completely new load. If new, provide a panel schedule using NEC 220 to show this added load can adequately be supplied by the existing service panel. |
||
| 04/10/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |