Please resubmit addressing the following comments:

1) The installation guide provided does not show the UL certification. Provide Manufacturer Specifications of the EV charger to be used. Include any certifications to ensure that the EVSE is UL listed E404.14.1

2) EV charger must be GFCI-capable, alternatively provide a means of GFCI protection (including GFCI Overcurrent Protection Devices) 625.54

3) Provide a one-line diagram with all equipment to be installed (including CTs or electrical monitoring equipment) as a part of the EV charging system. Show the number of conductors required for this installation and the conduit size to determine conduit fill does not exceed 40%. Include EGC and grounded conductors. See link for an example (This software is not required for approval; This is an example of a one-line diagram): https://www.kopperfield.com/single-line-diagram