Permit Number: TC-RES-0426-01767
Parcel: 133331830

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.1

Permit Number - TC-RES-0426-01767
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/09/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/09/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) Please clarify scope of work, description seems to indicate a service panel replacement, and the plans seem to show only the main disconnect will be replaced.
2) A Surge Protection Device (SPD) must be identified on the plans if a service panel replacement will be conducted. This requirement can be satisfied by providing the manufacturer’s specifications for the SPD to verify that it is UL listed and code compliant E606.5 NEC 230.67
04/09/2026 PDSD Application Completeness Express REVIEW COMPLETED