Permit Number: TC-RES-0426-01726
Parcel: 110063890

Address:
3044 N DESERT DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0426-01726
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/24/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/24/2026 Light Residential Building Review (OIP) Express REQUIRES RESUBMIT If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov

Please resubmit addressing the following comments:
1) According to the plans submitted, an EV charger is declared on the Load calculations. This has not been permitted, and a condition has been added to the permit that this Trade will not be issued until the EVSE is added to the scope of this trade or a separate trade is issued addressing the EVSE installation. If the EVSE is to be removed, please make a note of this on your resubmittal.

2) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the name/model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA and be UL 1449. 230.67
04/23/2026 PDSD Application Completeness Express REVIEW COMPLETED