Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.2
Permit Number - TC-RES-0426-01726
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/24/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/24/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | If you have questions regarding this Review, please contact Juan Quintana at juan.quintana@tucsonaz.gov Please resubmit addressing the following comments: 1) According to the plans submitted, an EV charger is declared on the Load calculations. This has not been permitted, and a condition has been added to the permit that this Trade will not be issued until the EVSE is added to the scope of this trade or a separate trade is issued addressing the EVSE installation. If the EVSE is to be removed, please make a note of this on your resubmittal. 2) Please provide the specifications of the SPD to be install, this can be done by showing the data sheet provided by the manufacturer or by listing the name/model number of the individual unit. SPD must have a nominal discharge current rating not less than 10kA and be UL 1449. 230.67 |
||
| 04/23/2026 | PDSD Application Completeness Express | REVIEW COMPLETED |