Permit Number: TC-RES-0426-01708
Parcel: 136238150

Address:
2963 S FOSTER DR

Review Status: Requires Resubmit

Review Details: RESIDENTIAL ADD/ALT v.1

Permit Number - TC-RES-0426-01708
Review Name: RESIDENTIAL ADD/ALT v.1
Review Status: Requires Resubmit
Review Date Reviewer's Name Type of Review Description Status Comments
04/21/2026 Residential Zoning APPROVED
04/21/2026 Bldg Permits - Post Review Express PENDING ASSIGNMENT
04/21/2026 Residential Building - Standard REQUIRES RESUBMIT TC-RES-0426-01708
PLAN REVIEW COMMENTS

Plan review for the above referenced structure has been completed. This letter reflects comments to be addressed. For facilitating a shorter back check time, please provide updated plans and calculations with a written response to each of the notated items indicating action taken. Do not cloud the changes made for comment revisions.

SCOPE OF REVIEW:

The scope of this plan review covers architectural, plumbing, mechanical, energy conservation and electrical. All code references are to the 2024 International Residential Code. All features were checked only to the extent allowed by the submittals provided. All portions of this project are assumed to meet or will meet other departmental requirements, conditions, and concerns before permit approval.

PROVIDE A COMPLETE PLAN SET showing all proposed alterations to the building with 2024 IRC code compliance with component sizes.

Provide a response letter on separate file when submitting the updated construction plan set.

SITE PLAN:

1. Show the location of the electrical line, R106.1.1.

SECTIONS - DETAILS:

1 Specify method of transferring lateral forces from the roof diaphragm to the supporting structural elements (without fascia end-grain nailing), R801.2. Remove Detail #6/S1.0.
2 Show an appropriate load bearing connection, R802.6.
3 Identify all fasteners for wind loading compliance. Show post cap hardware with appropriate uplift capacity, R802.11.

ELECTRICAL PLANS:

1. Show any electrical alterations.
2. The overhead service conductor over the proposed building requires an 8’ clearance above the roof, E3604.2.1. Check with TEP customer service for service line options. https://www.tep.com/electric-service-requirements

If you have any questions, please contact:
Kenneth.VanKarsen@tucsonaz.gov
City of Tucson Residential Plan Review