Permit Number: TC-RES-0426-01677
Parcel: 125050900

Address:
2348 E 4TH ST

Review Status: Approved

Review Details: RESIDENTIAL SIMPLE REVIEW v.2

Permit Number - TC-RES-0426-01677
Review Name: RESIDENTIAL SIMPLE REVIEW v.2
Review Status: Approved
Review Date Reviewer's Name Type of Review Description Status Comments
04/07/2026 Light Residential Building Review (OIP) Express APPROVED E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3.

E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load.

E3606.5.2 Type: the SPD shall be a Type 1 or Type 2 SPD.

E3606.5.3 Replacement: Where service equipment is replaced, all of the requirements of this section shall apply.



2023 NEC 230.67 mandates whole-house surge protection (SPD) for services supplying dwelling units, dormitories, hotel/motel guest rooms, and patient rooms in nursing homes, requiring a Type 1 or Type 2 SPD, often built-in or next to the service, with a minimum 10kA nominal discharge current rating, and also applies to service replacement, expanding on the 2020 code's requirement for just dwelling units.
04/07/2026 Bldg Permits - Post Review Express REVIEW COMPLETED
04/06/2026 PDSD Application Completeness Express REVIEW COMPLETED