Permit Review Detail
Review Status: Requires Resubmit
Review Details: RESIDENTIAL SIMPLE REVIEW v.1
Permit Number - TC-RES-0426-01619
Review Name: RESIDENTIAL SIMPLE REVIEW v.1
Review Status: Requires Resubmit
| Review Date | Reviewer's Name | Type of Review | Description | Status | Comments |
|---|---|---|---|---|---|
| 04/03/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/03/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Each address needs it's own permit. Surge Protection Device required for all panel upgrades. E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3 (Provide Surge Protection as required per 2023 NEC 230.67, NEC 230.67(D)). E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load. E3606.5.2 Type: the SPD shall be a Type 1 or Type 2 SPD. E3606.5.3 Replacement: Where service equipment is replaced, all of the requirements of this section shall apply. |
||
| 04/03/2026 | PDSD Application Completeness Express | REQUIRES RESUBMIT | If you have questions, please contact our team at PDSD-Permits@tucsonaz.gov. Each address needs to have its own trade permit. Please apply for a separate permit for 330 N CHERRY AV TUCSON, AZ 85719. |