| 04/02/2026 | Bldg Permits - Post Review Express | PENDING ASSIGNMENT | |||
| 04/02/2026 | Light Residential Building Review (OIP) Express | REQUIRES RESUBMIT | Panel upgrade comments Please show or describe how Whole home surge protection will be installed in the panel and re submit. Code references from the 2024 IRC & 2023 NEC below. If you have any questions, you can reach me at Zane.aouane@tucsonaz.gov E3606.5 Surge protection: all services supplying dwelling units shall be provided with a surge-protective device (SPD) installed in accordance with Sections E3606.5.1 through E3606.5.3. E3606.5.1 Location: the SPD shall be an integral part of the service equipment or shall be located immediately adjacent, if not located at each next-level distribution equipment downstream toward the load. E3606.5.2 Type: the SPD shall be a Type 1 or Type 2 SPD. E3606.5.3 Replacement: Where service equipment is replaced, all of the requirements of this section shall apply. |
||